Multi-stage refrigeration system centrifugal compressor repair instructions
After the centrifugal compressor of the cascade refrigeration system is disassembled, the dimensions of each journal (cooperating with the impeller, bearing, coupling, etc.) are measured with an outer diameter micrometer to calculate the roundness and cylindricity deviation. The value should be Within the allowable range. When the tolerance is large, check if the straightness deviation of the spindle is too large. Place the spindle in the casing or place it on the top of the lathe so that the spindle is in a free state. Use a dial gauge to measure the radial runout of the spindle journal.
The centrifugal compressor of the cascade refrigeration system is divided into 4-8 equal parts, and the rotor is driven according to the direction of rotation of the rotor. The large value of the dial gauge swing is the radial circle runout value. At the same time, the straightness deviation of the main shaft is measured at the appropriate position of the main shaft with two dial gauges, and the radial runout value should be no more than 0.01mm. If the over-standard is too large, the main shaft should be replaced.
Check the surface of the journal of the centrifugal compressor of the cascade refrigeration system for scratches, grooves, scratches, grinding points, etc. If necessary, perform flaw detection. Small defects can be scraped and polished by hand; large defects It can be repaired by surfacing, electroplating, spraying, etc., and then ground and polished. When the flaw detection reveals cracks or serious defects, it is generally not repaired and replaced.
At the same time, the end face runout of the centrifugal compressor impeller of the cascade refrigeration system should be measured, and the value should be within the allowable range. If the value of the end face jump exceeds the allowable range value, when the over-standard is small, the repair is generally not performed. When the value is large, the assembly relationship between the impeller and the main shaft can be adjusted by the method of adding the gasket. The impeller should be dynamically balanced and statically balanced after the overhaul. test.
The parts and fittings of the centrifugal compressor of the cascade refrigeration system have the specified technical standards and requirements for use. In the absence of reliable basis, it is necessary to strictly abide by these standards and never lower the standard.
The cascade refrigeration system should have a fixed maintenance and repair plan, carefully learn the correct understanding and use of equipment requirements by the user, and timely cooperate with the on-site user for regular maintenance.
Raccomandazioni correlate
-
L'influenza dell'evaporatore del termostato a semiconduttore sull'effetto di refrigerazione
1464I diversi modelli di apparecchiature per la termostatazione dei semiconduttori hanno diverse opzioni per l'evaporazione. In base ai diversi modelli, la scelta dell'evaporatore è diversa. Ad esempio, le apparecchiature termostatiche a semiconduttore di tipo box utilizzano un serbatoio d'acqua...
Visualizza dettagli -
Description of pump selection in steam-saturated system temperature control unit
1624The steaming system temperature control unit is one of the more used equipment in the pharmaceutical chemical industry. The performance of the LNEYA steaming system temperature control unit depends on the design of the whole system and the specifi...
Visualizza dettagli -
Guasti dei circolatori di riscaldamento e raffreddamento
1521Il circolatore di riscaldamento e raffreddamento può essere utilizzato in molti laboratori chimici e farmaceutici. Come risolvere i guasti del circolatore di riscaldamento e raffreddamento? Guasto della pompa di circolazioneIl guasto della pompa di circolazione è generalmente il calore...
Visualizza dettagli -
Istruzioni per il blocco delle macchine integrate ad alta e bassa temperatura
1552Se l'apparecchiatura della macchina integrata ad alta e bassa temperatura è in funzione per molto tempo, se non viene curata, può causare il blocco dell'apparecchiatura della macchina integrata ad alta e bassa temperatura. Come risolvere il blocco dell'apparecchiatura? La prima...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore