Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Raccomandazioni correlate
-
Maintenance of vacuum pump for fully enclosed heating and cooling circulator
1103Each accessory in the fully enclosed heating and cooling circulator constitutes the entire refrigeration heating and temperature control system. The performance of the pump is also very important. How to make the maintenance of the pump? For the f...
Visualizza i dettagli -
Semiconductor laser automatic temperature control equipment accessories fault solution
1128Semiconductor laser automatic temperature control compressor frosting, may be circulating water circulation or valve is not open, check the water valve, all pipelines, to ensure smooth, install short-circuit pipeline. It may be that the circulatin...
Visualizza i dettagli -
Knowledge sharing of high-power chiller pipeline cleaning
880For many companies, due to the weak awareness of daily maintenance of high-power chillers, industrial high-power chillers have not been effectively maintained for a long time. If the industrial high-power chillers lacks the necessary maintenance, ...
Visualizza i dettagli -
Accurate temperature control for battery testing to improve the performance of electric vehicles
822Electric vehicles (EVs) have completely transformed the automotive industry, providing a more sustainable and energy-efficient mode of transportation. One of the basic components of electric vehicles is their rechargeable battery. Electric v...
Visualizza i dettagli