What are the common debugging problems in low temperature refrigeration baths?
When the low-temperature cooling bath is in debugging, if the local cooling effect is not good, the system may be blocked by foreign matter or the system design is unreasonable and cannot be adjusted normally. At this time, LNEYA removes foreign matter and thoroughly cleans it to adjust the slope of the pipeline.
When debugging, it is found that the vibration and noise of the pump are large when it is running. It may be that the axial and radial deviation of the coupling is large. It may be that the pump flange is too large and the anchor bolts are unevenly stressed. It is the natural vibration frequency of the pump and the pipeline that cause resonance. At this time, the axial and radial deviation of the coupling are adjusted quickly. Adjust the natural vibration frequency between the pump and the pipe, install the relevant soft joint parts, replace the flange and make the anchor bolts evenly.
During commissioning, it was found that the cooling capacity could not reach the required fixed value. It may be that the cooling tower water temperature did not reach the specified cooling parameter, or the pump output was insufficient, or the condenser isolation gasket was misplaced and could not be cooled, or the pipeline in the condenser was blocked. Repair the cooling tower to meet the water temperature and water requirements, remove foreign matter in the pipeline, and check if the condenser isolation gasket is misaligned.

If the exhaust pressure is too high, it is necessary to pay attention to whether the cooling water is insufficient, whether the condensation in the condenser heat transfer tube is serious, whether the cooling water temperature is too high, whether there is too much air in the system, check the cause, repair the cooling tower, and heat transfer of the condenser. The tube is cleaned to remove air from the system.
If severe frost formation is found, check if the return air filter is clogged, if the exhaust air volume is loose after the fan belt is loose, and if the return air valve is too small, it is recommended to clean the return air filter and adjust the fan belt. Adjust the size of the return air valve.
Common faults encountered in the commissioning of these low-temperature refrigeration baths, we try to check them before debugging, try to avoid these faults.
Raccomandazioni correlate
-
Introduzione di frigoriferi per pezzi metallici come i cuscinetti surgelati
819Il box criogenico LNEYA per il congelamento continuo dei pezzi ha una velocità di raffreddamento rapida e la bassa temperatura può raggiungere i -150℃. Può essere utilizzato per l'assemblaggio a freddo di cuscinetti e parti meccaniche. Il trattamento criogenico può migliorare le proprietà meccaniche...
Visualizza i dettagli -
What Is The Effect Of Small Water Cooled Chiller On Industrial Production?
1131The small water cooled chiller is used in a wide range of applications, such as the food processing industry and the pharmaceutical processing industry. In some industrial fields, small water cooled chillers are often required. The application of ...
Visualizza i dettagli -
Istruzioni per il test dei componenti delle società di ispezione dei trucioli
973Con il continuo sviluppo dell'industria del collaudo dei componenti, sono nate aziende di collaudo dei chip e anche LNEYA ha introdotto apparecchiature per il collaudo dei chip. Il vettore di test della società di controllo dei chip è...
Visualizza i dettagli -
-20 ° C freezer manufacturers choose what to look at the evaporator?
1189In the process of producing industrial freezer, the selection of a suitable evaporator is also very important for the freezer, because the choice of suitable evaporator is better for better operation of the -20 °C freezer. The evaporator is genera...
Visualizza i dettagli