Introduzione all'uso del refrigeratore di precisione a prova di esplosione
Wuxi Lneya solves the problem of how to charge refrigerants in the absence of refrigeration.
1. Connect all kinds of equipment well, close the three valve when the vacuum pressure is down to 133.3Pa, remove the hose from the suction port of the vacuum pump, connect it on the R404 cylinder, and release the hose on the three valve.
2. Open the handle on the R404 cylinder slightly, and when the R404 refrigerant sprayed out of the loosened hose, the loosened hose was quickly fastened to the three valve (this is to remove the residual air in the hose).
3. Invert the R404 gas cylinder, the explosion proof precision chiller compressor is electrified, and the power line is put into the clamp type ammeter. Open the three-way valve handle so that the compressor can quickly shut down after inhaling part of the R404 refrigerant. Observe the pressure gauge pressure and the clamp ammeter, and the three valve handles are reopened after the pressure and current are reduced. After filling a part of the R12 refrigerant, the handle of the three valve is quickly closed, repeated so several times.
4. Through comprehensive observation: the pressure of the pressure gauge is stable at 0.03-0.05MPa (0.02-0.04MPa in winter and 0.05-0.07 MPa in summer). When the current of the clamp ammeter is steady at 0.6-0.8A, the condenser is evenly distributed and the filter temperature is slightly higher than the ambient temperature. The evaporator surface is evenly frosted and it will feel sticky. At this time, the amount of refrigerant charge is appropriate, that is, the capillary can be compressed by sealing pliers, then the capillary can be clipped by wire clamp and welded by oxygen welding at the fracture.
5. The soapy water is used to check the welding place.
Follow the steps and the refrigerant filling of the explosion-proof precision chiller should be completed basically, but it needs to be paid attention to that the refrigerant should not be overcharged at once in order to avoid failures.
Raccomandazioni correlate
-
How to use the 4kW new energy charging pile cooling system?
13194kW liquid cooling chiller for new energy charging pile
Visualizza dettagli -
Various reactors and materials use PLC temperature control system
1855The PLC temperature control system is used for the lifting and constant temperature control of glass reactors, metal reactors and bioreactors, especially for heat exothermic control in the reaction process. The heat transfer oil in the jacket of t...
Visualizza dettagli -
Teoria del flusso del ghiaccio, qualità dell'acqua ghiacciata, flusso e pressione della macchina per il ghiaccio.
1342The softening of water is also an important problem in the process of using chillers.The pH value of water also needs to be continuously observed. The optimum pH value should be equal to 7. The pH value greater than 7 will cause terrible corrosion...
Visualizza dettagli -
Il ruolo del sistema di controllo della temperatura TCU nel reattore chimico e farmaceutico
2076Il controllo della temperatura del bollitore di reazione nella ricerca e sviluppo di farmaci e negli esperimenti chimici, così come il controllo della temperatura nella produzione sperimentale su piccola scala e nei processi di produzione industriale, richiedono una tempera...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore