FLT-100℃~90℃ low temperature cascade
  • Precisione della temperatura±0.1℃
  • Controllo del flusso12~45/min
  • TipoFrequency Variable Series
  • Gamma di potenza380V

FLTZ -100℃~+90℃ Low Temperature Cascade Refrigeration Series

Modello FLTZ-002 FLTZ-003 FLTZ-004 FLTZ-006 FLTZ-008 FLTZ-010 FLTZ-015
FLTZ-002W FLTZ-003W FLTZ-004W FLTZ-006W FLTZ-008W FLTZ-010W FLTZ-015W
Intervallo di temperatura 5℃~90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Cooling capacity @10℃ 6kW 8kW 10kW 15kW 20kW 25kW 40kW
Internal circulating fluid volume 4L 5L 6L 8L 10L 12L 20L
Volume del vaso di espansione 10L 10L 15L 15L 20L 25L 35L
Refrigerante R410A
Refrigerating medium Silicone oil, fluorinated liquid, polyol aqueous solution, DI, etc. (DI temp needs to be controlled above 10 ℃)
Dimensioni del collegamento ZG1/2 ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1
Cooling water connection size ZG1/2 ZG1/2 ZG3/4 ZG1 ZG1 ZG1 ZG1 1/8
Flusso di acqua di raffreddamento @20℃ 1,5 m³/h 2m³/h 2,5 m³/h 4m³/h 4,5 m³/h 5,6 m³/h 9m³/h
Process temperature control The remote target temperature can be controlled by combining the self created model free self
 built tree algorithm and cascade algorithm
Dimensioni cm 950*380*1055 950*380*1055 950*380*1055 980*430*1400 980*430*1400 1080*600*1500 1080*600*1500

Modello FLTZ-1002W FLTZ-1004W
Intervallo di temperatura  -100℃~+90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Controllo del flusso 7~25L/min 12~45L/min
Cooling capacityat-90℃ 1,5kW 3kW
Capacità di riscaldamento 3,5kW 5,5kW
Internal circulating fluid volume 5L 8L
Volume del vaso di espansione 10L 15L
Heat-conduction medium Liquido fluorurato
Dimensioni del collegamento ZG3/4 ZG3/4
Cooling water connection size ZG3/4 ZG1
Cooling water@20℃ 50L/min 2bar~7bar 100L/min 2bar~7bar
Circuit breaker 32A 63A
Process temperature control The remote target temperature can be controlled by combining the self created model free self
 built tree algorithm and cascade algorithm
FLTZ -45℃~90℃

Modello FLTZ-002 FLTZ-003 FLTZ-004 FLTZ-006 FLTZ-008 FLTZ-010 FLTZ-015
FLTZ-002W FLTZ-003W FLTZ-004W FLTZ-006W FLTZ-008W FLTZ-010W FLTZ-015W
Intervallo di temperatura 5℃~90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Cooling capacity @10℃ 6kW 8kW 10kW 15kW 20kW 25kW 40kW
Internal circulating fluid volume 4L 5L 6L 8L 10L 12L 20L
Volume del vaso di espansione 10L 10L 15L 15L 20L 25L 35L
Refrigerante R410A
Refrigerating medium Silicone oil, fluorinated liquid, polyol aqueous solution, DI, etc. (DI temp needs to be controlled above 10 ℃)
Dimensioni del collegamento ZG1/2 ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1
Cooling water connection size ZG1/2 ZG1/2 ZG3/4 ZG1 ZG1 ZG1 ZG1 1/8
Flusso di acqua di raffreddamento @20℃ 1,5 m³/h 2m³/h 2,5 m³/h 4m³/h 4,5 m³/h 5,6 m³/h 9m³/h
Process temperature control The remote target temperature can be controlled by combining the self created model free self
 built tree algorithm and cascade algorithm
Dimensioni cm 950*380*1055 950*380*1055 950*380*1055 980*430*1400 980*430*1400 1080*600*1500 1080*600*1500

Modello FLTZ-202 FLTZ-203 FLTZ-204 FLTZ-206 FLTZ-208 FLTZ-210 FLTZ-215
FLTZ-202W FLTZ-203W FLTZ-204W FLTZ-206W FLTZ-208W FLTZ-210W FLTZ-215W
Intervallo di temperatura  -25℃~90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Controllo del flusso 10~25L/min 15~45L/min 25~75L/min
Cooling capacity @-15℃ 2kW 3kW 3,8kW 6kW 7.6kW 10kW 15kW
Internal circulating fluid volume 4L 5L 6L 8L 10L 12L 20L
Volume del vaso di espansione 10L 10L 15L 15L 20L 25L 35L
Refrigerante R404A
Refrigerating medium Silicone oil, fluorinated liquid, glycol solution etc
Dimensioni del collegamento ZG1/2 ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1
Cooling water connection size ZG1/2 ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 1/8
Flusso di acqua di raffreddamento @20℃ 1,2 m³/H 1,6 m³/H 2,6 m³/H 3,6 m³/H 5,5 m³/H 7m³/H 10,2 m³/H
Process temperature control The remote target temperature can be controlled by combining the self created model free self
 built tree algorithm and cascade algorithm
Dimensioni cm 950*380*1055 950*380*1055 950*380*1055 980*430*1400 980*430*1400 1080*600*1500 1080*600*1500
Modello FLTZ-402 FLTZ-403 FLTZ-404 FLTZ-406 FLTZ-408 FLTZ-410 FLTZ-415
FLTZ-402W FLTZ-403W FLTZ-404W FLTZ-406W FLTZ-408W FLTZ-410W FLTZ-415W
Intervallo di temperatura  -45℃~90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Controllo del flusso 10~25L/min  5bar max 15~45L/min 5bar max 25~75L/min 5bar max
Riscaldamento Using compressor heating, prevent condenser frosting technology
Cooling capacity @-35℃ 1kW 1,4 kW 1,8kW 2,5kW 3,3 kW 5kW 8kW
Internal circulating fluid volume 4L 5L 6L 8L 10L 12L 20L
Volume del vaso di espansione 10L 10L 15L 15L 20L 25L 35L
Refrigerante R404A
Refrigerating medium Silicone oil, fluorinated liquid, glycol solution etc
Dimensioni del collegamento ZG1/2 ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1
Cooling water connection size ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 ZG1 1/8
Flusso di acqua di raffreddamento @20℃ 1,5m³/H 2,4 m³/H 3,5 m³/H 5m³/H 5,5 m³/H 6m³/H 8m³/H
Process temperature control The remote target temperature can be controlled by combining the self created model free self
 built tree algorithm and cascade algorithm
Dimensioni cm 950*380*1055 950*380*1055 950*380*1055 980*430*1400 980*430*1400 1080*500*1500 1080*500*1500
Heat exchange Chiller Compressor-free

Modello ETCU-005W ETCU-015W ETCU-030W ETCU-050W ETCU-100W ETCU-200W ETCU-300W
Intervallo di temperatura Cooling water temperature +5℃~90℃
Precisione del controllo della temperatura ±0,05℃(Temperatura di uscita a stato stazionario)
Temperatura dell'acqua di raffreddamento 7℃~30℃ Cooling water flow is controlled by Siemens/Honeywell regulating valves
Capacità di raffreddamento 5kW 15kW 30kW 50kW 100kW 200kW 300kW
Test conditions: When the maximum circulation amount, the temperature difference between
the temperature control temperature and the cooling water temperature is 15℃
Pompa di circolazione 7~20L/min 5bar 15~40L/min 5bar 20~60L/min 5bar 40~110L/min 5bar 150~250L/min 5bar 250~500L/min 5bar 400~650L/min 5bar
Volume del serbatoio 5L 10L 20L 30L 60L 120L 240L
Dimensioni cm 480*750*390 480*750*390 480*750*500 Customization Customization Customization Customization

Applicazioni

Inviateci la vostra richiesta e vi contatteremo entro 24 ore.
*
*

Multi-channel

Channel 1Channel 2Channel 3

Voltage

50HZ single phase50HZ three phase60HZ single phase60HZ three phase*
Invio....
Inviato con successo!
Invio fallito! Riprovare più tardi
Errore e-mail!
Errore telefonico!

consigliare i prodotti

  • FLTZ -45℃~90℃"      /&gt;<figcaption><span>Metodo di riscaldamento entro 40 ℃ adotta un compressore di riscaldamento a gas caldo completamente chiuso, e la macchina funziona ininterrottamente per 24 ore Il dispositivo di controllo della temperatura dei semiconduttori Chiller è utilizzato principalmente per...</span></figcaption></figure></a></div><div class=FLTZ -45℃~90℃

    Metodo di riscaldamento entro 40 ℃ adotta un compressore di riscaldamento a gas caldo completamente chiuso, e la macchina funziona ininterrottamente per 24 ore Il dispositivo di controllo della temperatura dei semiconduttori Chiller è utilizzato principalmente per...

caricamento...

已经是到最后一篇内容了!