It needs to be used with ETCU heat exchange chiller.
Modello | FLTZ-203W/ETCU-008W | ||
Pipeline | channel 1 | channel 2 | channel 3 |
Intervallo di temperatura | -10℃~+60℃ | +30℃~+80℃ | -10℃~+80℃ |
Temperature stability | ±0.1℃(Customizable temperature control accuracy of ±0.01°C.) | ||
Capacità di raffreddamento | 4kW@-10℃/21kW@+20℃ | 6 kW@+30℃ | 3kW@-10℃ |
Capacità di riscaldamento | 4kW | 4.5+6kW | 3kW |
Heat conducting medium flow rate | 17L/min 0.7MPa | 17L/min 0.7MPa | 17L/min 0.7MPa |
Heat conducting medium connection size | ZG3/4 | ZG3/4 | ZG3/4 |
Ambient temperature | 10~35 ℃ | 10~35 ℃ | 10~35 ℃ |
Ambient humidity | 30~70% | 30~70% | 30~70% |
Cooling water flow rate | 15~20℃ | 15~20℃ | 15~20℃ |
Temperatura dell'acqua di raffreddamento | 30L/min@15~20℃ | 15L/min@15~20℃ | 15L/min@15~20℃ |
Interruttore automatico | 100A | ||
Peso | 600kg | ||
Dimensioni cm | 60*100*170 |
Modello | FLT-215W/ETCU-015W/ETCU-008W | ||
Pipeline | channel 1 | channel 2 | channel 3 |
Intervallo di temperatura | -20℃~+50℃ | +30℃~+100℃ | +30℃~+40℃ |
Temperature stability | ±0.1℃(Customizable temperature control accuracy of ±0.01°C.) | ||
Capacità di raffreddamento | 15kW@-10℃ | 13kW@PCW+15℃ | 8kW@PCW+10℃ |
Capacità di riscaldamento | 2kW | 6kW | Pump Heat Loss |
Heat conducting medium flow rate | 30L/min 0.85MPa | 30L/min 0.85MPa | 20L/min 0.8MPa |
Heat conducting medium connection size | ZG3/4 | ZG3/4 | ZG3/4 |
Ambient temperature | 10~35 ℃ | 10~35 ℃ | 10~35 ℃ |
Ambient humidity | 30~70% | 30~70% | 30~70% |
Cooling water flow rate | 15~20℃ | 15~20℃ | 15~20℃ |
Temperatura dell'acqua di raffreddamento | 30L/min@15~20℃ | 15L/min@15~20℃ | 15L/min@15~20℃ |
Interruttore automatico | 75A | ||
Peso | 600kg | ||
Dimensioni cm | 60*100*170 |
Only water-cooling models available
The three independent channels are usually designed as a modular structure, which can be used for expansion tanks, condensers, cooling water systems and other components. The compact structure reduces the footprint of the industrial chiller.
In addition, one host can independently control multiple channels, making operation easier and more convenient.
WeChat/Telefono
18914253067
+86 18914253067
Indirizzo e-mail
market@lneya.com
Perché scegliere LNEYA?
Get in touch with our Triple Channel chiller experts
Contatto LNEYA
Inviateci la vostra richiesta e vi contatteremo entro 24 ore.