The Phenomenon of Ice Jam in Low Temperature Chiller System
The phenomenon of ice jam in low temperature chiller system is mainly due to the excessive water in the refrigeration system. With the continuous circulation of refrigerants, the water in the refrigeration system gradually concentrates at the outlet of expansion valve. Because the outlet of expansion valve has the lowest temperature, the water turns into ice and the ice enlarges gradually. To a certain extent, the expansion valve will be completely blocked, resulting that the refrigerant can not be recycled, and the cold storage will not refrigerate.
The phenomenon of ice jam in basso temperature sistema di refrigerazione is normal in the initial stage. There is frost in the evaporator, heat dissipation of the condenser, stable operation of the unit, clear and stable movement of refrigerant in the evaporator. With the formation of ice jam, the air flow is gradually weakened and intermittent. When the jam becomes serious, the sound of air flow completely disappears. The refrigerant cycle is interrupted. And the condenser is gradually cooled.
Because of the blockage, the exhaust pressure rises. The sound of the machine increases. There is no refrigerant flowing into the evaporator. The frost area decreases gradually. The temperature increases gradually, and the temperature of the expansion valve rises together, so the ice begins to melt. At this time, the refrigerant begins to recycle again. After a period of time, ice blockage occurs again, forming a periodic phenomenon of through-blockage.
Troubleshooting of Ice Block
The ice jam failure of low temperature chiller system is due to excessive moisture in the system, so the whole refrigeration system must be dried. There are two ways to deal with it:
1. Heat and dry the components of the refrigerant system in a drying box. Remove the compressor, condenser, evaporator, expansion valve and return pipe in the refrigerant system from the cold storage and put them into the drying box for heating and drying.
2. Remove the water content of each part of the refrigeration system by heating and secondary vacuum extraction.
Raccomandazioni correlate
-
Manuale della macchina calda e fredda LNEYA SUNDI
2028The temperature range of the hot and cold machine ranges from -120 ° C to 350 ° C. It has superior performance and unique performance. It has high precision and intelligent temperature control. The high cooling power is from 0.5 to 1200 kW. High p...
Visualizza dettagli -
Analisi dei principi del refrigeratore a glicole
1595Glycol chiller is an industrial chillerwith glycol as refrigerant. The structure of glycol chiller is roughly the sameas that of ordinary industrial chiller, which is composed of compressor,evaporator, condenser and electric control system. ...
Visualizza dettagli -
Dual-channel chillers for semiconductor manufacturing industry
1555Dual-channel chillers are used in a variety of processes in the semiconductor manufacturing industry. The main purpose is to provide precise temperature control to ensure that the equipment in the semiconductor manufacturing process operat...
Visualizza dettagli -
Descrizione dei guasti comuni del gruppo frigorifero a semiconduttori LNEYA
2053Se si verifica un allarme di alta tensione nell'unità di refrigerazione dei semiconduttori, è necessario verificare se le tubazioni esterne sono bloccate o sporche. Pulire e rimuovere in tempo. Se si tratta di un dispositivo di refrigerazione a semiconduttori raffreddato ad aria, è necessario ...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore