Come risolvere il problema del consumo energetico della pompa centrifuga di raffreddamento?
Ci sono molte opportunità per la pompa centrifuga nel refrigeratore, ma il guasto della pompa centrifuga influenzerà l'uso del refrigeratore. Pertanto, non preoccupatevi se la potenza della pompa centrifuga aumenta, scoprite la causa in tempo e...
The cooling machine centrifugal pump works by rotating the impeller to make the water centrifugally. Before the pump starts, the pump casing and the suction pipe must be filled with water, and then the motor is started, so that the pump shaft drives the impeller and water to perform high-speed rotary motion. Centrifugal movement occurs, and is thrown to the outer edge of the impeller, and flows into the water pressure pipe of the water pump through the flow path of the volute pump casing.
The reasons for the increase in power are summarized below, as follows:
The matching of the cooling machine pump is unreasonable. The pressure and displacement of the modified pump or the replaced pump are improved compared with the original pump, and the power of the motor is too small; the outlet valve is too large and the pump pressure is too low. The pump displacement exceeds the specified value of the nameplate too much, and the deviation from the working point is too much; the cooling machine packing pressure is too tight; the cooling machine power supply voltage is too low, the current exceeds the rated value; the cooling motor or pump is seriously different, the vibration is serious; the pump The friction between the inner rotor and the stator component is severe; the rotor of the cooling motor is turbulent, the position is not correct, the journal step and the bearing end face or the coupling and the oil seal cover are ground; the cooling coupling coupling buffer damping rubber ring is too tight, and the pump pushes forward The motor coupling and the bearing cover are ground; the balance plate of the cooling machine is not opened, the grinding is severely performed, and the balance return pipe is hot; the radial clearance of the pressure relief sleeve or the balance plate is too small, the deflection is too large, and the operation is worn; When the cooling pump is started, serious internal faults occur, such as the mouth ring, the bushing falling off or the matching clearance is too small; the pump shaft is too rigid and bending deformation.
In the face of the above-mentioned failure of the centrifugal pump of the cooling machine, according to the situation on the site, timely take corresponding measures to deal with it, get in touch with the power supply unit, and adjust the supply voltage to within the specified range;
Adjust the opening degree of the outlet valve to make it run at the normal working condition; properly control the pump pressure and displacement, reduce the running current of the motor; adjust the tightness of the packing gland.
If the above measures can not be eliminated, the pump should be stopped for inspection and treatment. Specific treatment measures: 1 re-empting and draining the air inside the pump; 2 checking and adjusting the lubricating oil pressure, repairing or replacing the bearing bush; 3 replacing the coupling minus Shock rubber ring; 4 repair or replace the balance plate; 5 to carry out three guarantee operations, repair and replace damaged parts; 6 with the professional team to deal with motor failure.
If you still can’t solve the cooling centrifugal pump in time, contact the professional manufacturer for technical guidance!
Raccomandazioni correlate
-
Guasto al compressore del sistema di controllo della refrigerazione causato dalla pressione dell'olio
1628Se non c'è pressione dell'olio nel sistema di controllo della refrigerazione, controllare il collegamento del sistema di tubazioni della pompa dell'olio per verificare che non ci siano perdite d'olio o blocchi. Se il collegamento è allentato, è necessario stringere il giunto. Se è bloccato, la conduttura dell'olio deve essere liberata...
Visualizza dettagli -
L'importanza del controllo della temperatura per la lavorazione delle piante di cannabis
1499The legalization of industrial hemp in Europe, America and other countries has increased the demand for equipment for hemp processing. Cannabis eventually comes in the form of CBD extract. In order to convert the plant into a concentrate for medic...
Visualizza dettagli -
Nota di spegnimento della condensazione della purificazione dei rifiuti organici
1895Se il gas di scarico organico viene purificato e condensato, se si verifica un guasto durante il funzionamento, deve essere spento e smaltito in tempo. Allora, come può essere utilizzato il sistema di purificazione e condensazione dei rifiuti organici LNEYA una volta spento? L'or...
Visualizza dettagli -
Unità di raffreddamento a bassa temperatura nella produzione di materiali ausiliari per catalizzatori PGA
1276I refrigeratori a bassa temperatura svolgono un ruolo importante nel processo di reazione di produzione dell'acido poliglicolico (PGA) e dei suoi catalizzatori e additivi. La sintesi e il processo di post-trattamento dell'acido poliglicolico comportano spesso reazioni esotermiche, ...
Visualizza dettagli