Causes and troubleshooting of low-temperature water chillers for photoetching machines
The operator of the low-temperature chiller for lithography machine can have a certain understanding of the related faults and solutions during the operation of the equipment, so as to better use the low-temperature chiller for lithography machine. What is the cause of the failure?
1. Refrigerant leakage:
After the refrigerant leaks in the system, the cooling capacity is insufficient, the suction and discharge pressures are low, the evaporator is not covered with frost or there is a small amount of frost at the corners, if the expansion valve hole is adjusted, the suction pressure still does not change much, and the system is balanced after shutdown The pressure is generally lower than the saturation pressure corresponding to the same environment.
Elimination method: After the refrigerant leaks, do not rush to fill the system with refrigerant, but immediately find the leakage point, and then fill the refrigerant after repair.
2. Too much refrigerant is charged after maintenance:
The amount of refrigerant charged in the refrigeration system after maintenance exceeds the capacity of the system, the refrigerant will occupy a certain volume of the condenser, reduce the heat dissipation area, and reduce the cooling effect. The suction and discharge pressures are generally higher than the normal pressure. Value, the evaporator is not frosting, and the lithography machine uses a low temperature chiller to cool down slowly.
Remedy: According to the operating procedure, the excess refrigerant must be discharged from the high shut-off valve after a few minutes of shutdown. At this time, the residual air in the system can also be discharged.
3. There is air in the refrigeration system:
Air in the refrigeration system will reduce the refrigeration efficiency. The prominent phenomenon is that the suction and discharge pressures increase (but the discharge pressure has not exceeded the rated value), and the temperature from the compressor outlet to the condenser inlet increases significantly. Air, exhaust pressure and exhaust temperature all increase.
Remedy: A few minutes after the shutdown, air can be discharged from the high-pressure shut-off valve several times in succession, and some refrigerant can be properly filled according to the actual situation.
4. The frost on the surface of the evaporator is too thick:
The cold storage evaporator used for a long time should be defrosted regularly. If it is not defrosted, the frost layer on the evaporator pipe will become thicker and thicker. When the entire pipe is wrapped into a transparent ice layer, it will seriously affect the heat transfer and cause the lithography machine The temperature of the low-temperature chiller does not fall within the required range.
Remedy: Stop the machine to defrost, and do not hit the frost layer with iron or wooden sticks to prevent damage to the evaporator pipeline.
5. There is refrigerating oil in the evaporator pipeline:
During the refrigeration cycle, some refrigerating oil remains in the evaporator pipeline. After a long period of use, when there is a large amount of residual oil in the evaporator, it will seriously affect the heat transfer effect and cause poor cooling.
Remedy: Remove the refrigerant oil in the evaporator. Remove the evaporator, blow it out, and then dry it.
After the low-temperature chiller for lithography machine has a liquid hammer failure, if the operator or user cannot solve it in time, please contact the manufacturer to solve it.
to sum up
We must clean up and maintain the equipment in time, so as to enhance the life of the equipment.
Raccomandazioni correlate
-
Nuovo sistema di rilevamento della batteria di alimentazione dell'auto di energia descrizione del vuoto
1746Il test della batteria di alimentazione del veicolo a nuova energia controlla che l'interruttore della pompa a vuoto sia chiuso prima del funzionamento; quando la pompa a vuoto è posizionata orizzontalmente, assicurarsi che l'olio lubrificante e la linea di livello dell'olio siano mantenuti orizzontali; se...
Visualizza dettagli -
Cosa succede al raffreddamento eccessivo del refrigeratore a bassa temperatura?
1439Come tutti sanno, il refrigeratore a bassa temperatura è un tipo di progetto di refrigerazione professionale ampiamente utilizzato nell'industria. Sebbene sia in grado di fornire un ambiente criogenico efficace, si verificano alcuni fenomeni anomali di sovraraffreddamento. Di solito, il refrigeratore a...
Visualizza dettagli -
Diversi aspetti di attenzione del congelatore a bassissima temperatura
1745Le prestazioni dei congelatori a bassissima temperatura si riducono naturalmente a causa dell'applicazione prolungata in tutti i campi. Pertanto, Guanya Refrigeration Technology Co., Ltd, leader nella produzione di congelatori a bassissima temperatura, ricorda a tutti gli utenti...
Visualizza dettagli -
What Should Be Noticed In Detail When Installing A Precision Chiller?
1840First, when installation, everyone needs to check whether your cold water machine works normal, whether the accessories are all right, whether there is damage, so as to avoid problems in installation. Second, when installing, the site of the preci...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore