Come risolvere il problema della brinatura del dispositivo di circolazione a bassa temperatura?
The failure of the low temperature circulation device frosting is mainly because the compressor return air temperature is too low, which may be that the throttle valve liquid refrigerant supply is in a normal state in the low temperature circulation device, but the low temperature circulation device evaporator cannot normally absorb the heat supply refrigerant expansion; It may also be because the evaporator is in a normal working state but the refrigerant supply throttle valve is too large, causing the low pressure to cause the compressor return air temperature to be too low.
After a little frosting, because the heat insulation layer on the surface of the evaporator has low heat, the refrigerant will transfer to other areas after expansion, causing frosting in the evaporator of the low-temperature circulation device, which will cause the low-temperature circulation device to evaporate. The insulation layer appears to expand to the compressor return pipe causing the compressor to return to air and frost. When the low temperature circulation device has less refrigerant, it is found that the low pressure of the evaporator causes the evaporation temperature to be low, so that the expansion point of the frost layer on the surface of the evaporator is transferred to the compressor return air to cause frosting of the compressor.
In the face of such a phenomenon of frosting of the compressor, Wuxi Yuze suggested that if the system has a heat exchanger bypass valve, then it is only necessary to adjust the hot gas bypass valve. The low temperature circulation device is running this process.
Open the rear end cover of the hot gas bypass valve of the low temperature circulation device, and then use the hex wrench of the toolbox to turn the adjusting nut clockwise. The adjustment process of the defrosting process should not be too fast. Generally, the half cycle is suspended. Let the low temperature circulation device refrigeration system run for a period of time and then look at the frost condition before deciding whether to continue to adjust. Wait for the low-temperature cycle device to run stably, and then tighten the end cap after the compressor frosting disappears. The defrosting process of the low-temperature cycle device can be solved!
For models below 15 cubic meters, since there is no hot gas bypass valve, if the frosting phenomenon is serious, the take-off pressure of the pressure switch of the condensing fan can be appropriately adjusted. specific method:
First find the pressure switch, remove the adjustment nut of the pressure switch to fix the small piece, then use a Phillips screwdriver to rotate clockwise, the whole adjustment also needs to be carried out slowly, adjust the half turn to see the situation and then decide whether it needs adjustment.
The low-temperature circulation device needs to pay attention when performing defrosting. When the model size of the equipment is very different, pay attention to the difference in details when repairing.
Raccomandazioni correlate
-
Vocs condensation adsorption technology energy control instructions
1834The vocs condensation adsorption technology has been developed under the current trend of environmental protection. The LNEYA vocs condensation adsorption technology uses condensation adsorption technology. In order to save operating costs, it is ...
Visualizza dettagli -
Come scegliere il prezzo del sistema a temperatura costante per semiconduttori?
1645Now, it can be said that most of the industrial production of various types require a semiconductor thermostat system to provide professional refrigeration, and an efficient semiconductor constant temperature system can provide great help for vari...
Visualizza dettagli -
Analisi delle cause dello scarso effetto di raffreddamento del refrigeratore ad acqua
1416I refrigeratori raffreddati ad acqua sono sempre più utilizzati in tutti gli ambiti della vita quotidiana. La sua funzione principale è quella di fornire acqua refrigerata industriale per apparecchiature o prodotti. L'intervallo di temperatura dell'acqua può essere regolato in base alle esigenze degli utenti,...
Visualizza dettagli -
Descrizione del compressore del dispositivo di prova del calore umido ad alta e bassa temperatura
1876I diversi tipi di compressori per i dispositivi di prova del calore umido ad alta e bassa temperatura hanno spesso un impatto sul prezzo. Al momento della scelta, dovremmo scegliere compressori di refrigerazione a basso consumo energetico il più possibile. Ora la Cina sta prestando sempre più attenzione...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore