Istruzioni operative dettagliate del refrigeratore industriale
The installation procedures of water
chiller include:
1. During installation, please check
whether the machine is damaged and select a suitable place for installation and
future maintenance. The site for installing the unit must be the floor or
installation pad, with a levelness within 6.4mm, and can bear the operating
weight of the unit.
2. The chiller shall be placed in the
machine room with room temperature of 4.4-43.3 ℃, and there shall be enough space around and above the unit for
daily maintenance.
3. At one end of the unit, a pipe
extraction space for cleaning the condenser tube bundle shall be reserved, and
door holes or other holes at appropriate positions can also be used.
4. Select water pipes with appropriate pipe
diameter, cooling system and cold water system when the unit operates at
maximum power, and connect them correctly.
5. For ordinary applications, the water
flow velocity through the evaporator and condenser is allowed to be between
1.0-3.6m/s.
6. The water flow shall be stable under any
load.
7. All cooling water pipes shall be
designed and installed according to the conventional method. The chilled water
pump shall be located on the inlet pipe of the chiller to ensure the positive
pressure and flow in the unit. When piping, damping pipes shall be set to
ensure proper elasticity, and prevent the water in the evaporator from being
drained when the water pump stops.
8. The pipeline shall be firmly supported
independent of the chiller to avoid stress on the components of the chiller.
9. In order to reduce noise and vibration,
it is better to install vibration isolator on the pipeline.
10. In order to use the chiller
economically and effectively, it is recommended to invite water treatment
experts to analyze the water supply quality of evaporator and condenser. Poor
water quality will cause scale, affect heat transfer, or produce corrosion
precipitation, affect the performance of the unit and increase operation and
maintenance costs.
11. Generally speaking, proper water
treatment and regular cleaning can maintain its good performance.
12. Please install a filter at the inlet of
the water pipe and clean it regularly.
13. After leak test, all nozzle openings
must be treated with rust prevention.
14. In order to facilitate daily
maintenance, the user can take some (or all) of the following measures: the
pressure gauge and stop valve with cock can be installed on the inlet and
outlet pipes of cooling water and chilled water, close to the chiller as far as
possible;
Lifting rails and beams can be erected
above the equipment to facilitate maintenance.
Raccomandazioni correlate
-
Low temperature cooling system exists in drying and freeze-drying equipment
1232In the drying and freeze-drying equipment, the low-temperature cooling system is one of the core components, which is crucial for achieving the freeze-drying process. Freeze drying (freeze-drying) is an effective method for removing moistu...
Visualizza dettagli -
Per quali strumenti può essere utile il refrigeratore a ricircolo da laboratorio LNEYA?
1329I refrigeratori a ricircolo per laboratorio trovano un'ampia gamma di applicazioni nella ricerca scientifica e nella produzione industriale, fornendo un controllo preciso della temperatura per vari esperimenti e strumenti. Di seguito sono riportati alcuni scenari comuni...
Visualizza dettagli -
How to judge the operating status of the chemical and pharmaceutical constant temperature control sy
1515Nowadays, many pharmaceutical and chemical industries use LNEYA's constant temperature control system. How to judge its operation status during operation? There should be no noise in the cylinder of the chemical and pharmaceutical thermostatic con...
Visualizza dettagli -
Reasons for the decrease of heat transfer effect of vertical ultra-low temperature refrigerator
1819If the outer frost layer of the vertical ultra-low temperature refrigerator is too thick or excessively dusty, it can be caused because the external temperature of the evaporator is mostly lower than 0 °C, resulting in low heat transfer efficiency...
Visualizza dettagli
Refrigeratori industriali LNEYA Produttore Fornitore