Micro-channel reactor thermostatically controlled air-cooled chiller compressor troubleshooting meth
The air-cooled chiller is a temperature
control device that is widely used in the microchannel reactor industry. Wuxi
Guanya LNEYA has produced a cold and heat source thermostatically controlled
air-cooled chiller for the microchannel reactor industry. If the compressor
fails during operation, it needs to be investigated and solved in time.
To troubleshoot the micro-channel reactor
thermostatically controlled air-cooled chiller compressor, first check the
circuit part to see if the equipment power supply, voltage, and switch are
normal; see if the equipment power supply is powered, the voltage is normal,
and the switch contacts are good , Whether the power supply lacks phase. When
the equipment is not equipped with an ammeter or a voltmeter, a multimeter or a
tester can be used to check the power supply. When the power supply voltage is
too low, the compressor cannot be started.
If the compressor of the micro-channel
reactor thermostatically controlled air-cooled chiller adopts a piston
compressor, whether the big end bearing bush and the curved sleeve of the
connecting rod are caught. These may be caused by the excessively high exhaust
temperature during the previous operation, or it may be caused by the coking of
the lubricating oil, which causes the cylinder and the piston to stick
together, which prevents the compressor from starting.
Check the thermostatically controlled
air-cooled water chiller differential pressure relay and high and low voltage
relay of the microchannel reactor. When the oil pressure of the compressor is
abnormal, the compressor can be stopped. At the same time, when the compressor
discharge pressure and suction pressure are abnormal, neither of them can be
started or the compressor will quickly stop running after it has been started.
Check whether the amount of chilled water, cooling water, and water temperature
are normal. If the water volume is small and the water temperature is high, it
will cause the condensing pressure to rise sharply and the evaporation
temperature to drop rapidly. Due to the action of the unit protection
facilities, the unit often shuts down quickly.
Check whether the solenoid valves and
regulating valves related to the equipment are malfunctioning, and whether they
are opened or closed as required. Check whether there is a leakage of working
fluid in the temperature sensing bag of the temperature relay, or the
adjustment is wrong.
Before use, the corresponding preparations
must be done well in order to run efficiently.
Raccomandazioni correlate
-
Characteristics of Industrial Constant Temperature Recirculating Chiller
1391Points for attention in the use ofindustrial constant temperature recirculating chillerIndustrial constant temperature recirculatingchillers are widely used in pharmaceutical, chemical and laboratory. Next,let's introduce the characteristics...
Visualizza i dettagli -
Analisi delle parti del refrigeratore a bassa temperatura
1126Il refrigeratore a bassa temperatura è un'apparecchiatura per il raffreddamento dell'acqua molto diffusa. Per questo motivo, quando lo si utilizza, è necessario prima comprendere il principio del refrigeratore d'acqua criogenico e dei suoi accessori, in modo da far funzionare il refrigeratore d'acqua criogenico in modo più efficiente...
Visualizza i dettagli -
Application of crystallization technology of ultra-low temperature chiller in petroleum industry
895This article mainly introduces the application of the freezing technology crystallization technology of industrial refrigerators in the oil industry and the principle of freezing crystallization. At present, the separation method using freeze crys...
Visualizza i dettagli -
What are the causes of corrosion in industrial chillers / water chillers?
1394Industrial chillers are now widely used in various industries, but as they become more and more widely used, many problems slowly emerge. Corrosion problems are also relatively common. Because everyone does not use the standard and the maintenance...
Visualizza i dettagli